Ambient temperature | 25 – 35 °C (77 – 95 °F) |
Engine rpm | At specified idle speed |
Blower fan motor switch | “H” (4th position) |
Temperature control | “Cool” |
Air outlet control | “Face” |
Vehicle doors | All open |
Air inlet door position | Recirculation |
Gauges should read as follows when ambient temperature is 30 °C (86 °F). | |
Pressure on high pressure gauge |
1480 – 1820 kPa
14.8 – 18.2 kg/cm² 210.5 – 259.0 psi |
Pressure on low pressure gauge |
290 – 390 kPa
2.9 – 3.9 kg/cm² 41.5 – 55.5 psi |
Gauges should read as follows when ambient temperature is 30 °C (86 °F). | |
Pressure on high pressure gauge |
1400 – 1750 kPa
14.0 – 17.5 kg/cm² 199.1 – 248.9 psi |
Pressure on low pressure gauge |
230 – 350 kPa
2.3 – 3.5 kg/cm² 32.7 – 49.8 psi |
Condition | Possible cause | Correction |
---|---|---|
Pressure is higher than acceptable range
(“A” area) |
Refrigerant overcharged | Recharge. |
Expansion valve frozen or clogged | Check expansion valve. | |
Clogged refrigerant passage of high side | Clean or replace. | |
Condenser cooling fan malfunction (Insufficient cooling of condenser) | Check condenser cooling fan. | |
Dirty or bent condenser fins (Insufficient cooling of condenser) | Clean or repair. | |
Compressor malfunction (Insufficient oil etc.) | Check compressor. | |
Engine overheat | Check engine cooling system referring to Engine Cooling System Inspection and Cleaning:M13A or Engine Cooling System Inspection and Cleaning:K9K . | |
Pressure is lower than acceptable range
(“B” area) |
Insufficient refrigerant (Insufficient charge or leakage) | Check for leakage, repair if necessary and recharge. |
Expansion valve malfunction (valve opens too wide) | Check expansion valve. | |
Compressor malfunction (Insufficient compression) | Check compressor. |
Condition | Possible cause | Correction |
---|---|---|
Pressure is higher than acceptable range
(“C” area) |
Expansion valve malfunction (valve opens too wide) | Check expansion valve. |
Compressor malfunction (Insufficient compression) | Check compressor. | |
Pressure is lower than acceptable range
(“D” area) |
Insufficient refrigerant (Insufficient charge or leakage) | Check for leakage, repair if necessary and recharge. |
Expansion valve malfunction (valve opens too narrow) | Check expansion valve. | |
Clogged refrigerant passage (crashed pipe) | Repair or replace. |
Condition | Possible cause | Correction |
---|---|---|
Crossing point is higher than acceptable range (“E” area) | Insufficient or excessive charge of refrigerant | Check refrigerant pressure. |
Dirty or bent A/C evaporator fins | Clean or repair. | |
Air leakage from cooling (heater) unit or air duct | Repair or replace. | |
Malfunctioning, switch over function of door in cooling (heater) unit | Repair or replace. | |
Compressor malfunction | Check compressor. | |
Crossing point is lower than acceptable range (“F” area) | Insufficient air volume from center duct (Heater blower malfunction) | Check blower motor and fan. |
Compressor malfunction | Check compressor. |
Condition | Possible cause | Correction | ||
---|---|---|---|---|
Manifold gauge | MPa (kg/cm²) (psi) | Detail | ||
Lo | Hi | |||
0.29 – 0.39
(2.9 – 3.9) (42 – 56) 0.27 – 0.37* (2.7 – 3.7)* (39 – 53)* |
1.48 – 1.82
(14.8 – 18.2) (211 – 259) 1.48 – 1.80* (14.8 – 18.0)* (211 – 256)* |
Normal condition | — | — |
Negative pressure |
0.5 – 0.6
(5 – 6) (71.2 – 85.3) |
The low pressure side reads a negative pressure, and the high pressure side reads an extremely low pressure.
Presence of frost around tubing to and from receiver/dryer and expansion valve. |
Dust particles or water droplets are either stuck or frozen inside expansion valve, preventing the refrigerant from flowing. |
Clean expansion valve.
Replace it if it cannot be cleaned. Replace receiver/dryer. Evacuate the A/C system and recharge with fresh refrigerant. |
Normal:
0.29 – 0.39 (2.9 – 3.9) (42 – 56) 0.27 – 0.37* (2.7 – 3.7)* (39 – 53)* ↑ ↓ Abnormal: Negative pressure |
Normal:
1.48 – 1.82 (14.8 – 18.2) (211 – 259) 1.48 – 1.80* (14.8 – 18.0)* (211 – 256)* ↑ ↓ Abnormal: 0.69 – 0.98 (7 – 10) (100 – 142) |
During A/C operation, the low pressure side sometimes indicates negative pressure, and sometimes normal pressure. Also high pressure side reading fluctuates between the abnormal and normal pressure. | Expansion valve is frozen due to moisture in the system, and temporarily shuts off the refrigeration cycle. |
Replace expansion valve.
Replace receiver/dryer. Evacuate A/C system and recharge with fresh refrigerant. |
0.05 – 0.15
(0.5 – 1.5) (4.2 – 21.3) |
0.69 – 0.98
(7 – 10) (100 – 142) |
Both low and high pressure sides indicate low readings.
Continuous air bubbles are visible through sight glass. Output air is slightly cold. |
Insufficient refrigerant in system
(Refrigerant leaking). |
Using leak detector, check for leaks and repair as necessary.
Recharge refrigerant to a specified amount. If the pressure reading is almost 0 when the manifold gauges are attached, check for any leaks, repair them, and evacuate the system. |
0.4 – 0.6
(4 – 6) (56.9 – 85.3) |
Pressure on low pressure side is high.
Pressure on high pressure side is low. Both pressure becoming equal right after A/C is turned OFF. |
Internal leak in compressor. | Inspect compressor and repair or replace as necessary. | |
0.35 – 0.45
(3.5 – 4.5) (50 – 64) |
1.96 – 2.45
(20 – 25) (285 – 355) |
Pressure on both low and high pressure sides is high.
Air bubbles are not visible even when engine RPM is lowered. |
Overcharged A/C system. | Adjust refrigerant to specified amount. |
Faulty condenser cooling operation. | Clean condenser. | |||
Faulty condenser cooling fan operation. | Inspect and repair condenser cooling fan. | |||
Pressure on both low and high pressure sides is high.
Low pressure side tubing is not cold when touched. Air bubbles are visible through sight glass. |
Presence of air in A/C system
(Improperly evacuated). |
Replace receiver/dryer.
Inspect quantity of compressor oil and presence of contaminants in oil. Evacuate system and recharge with fresh refrigerant. |
||
0.45 – 0.55
(4.5 – 5.5) (64 – 78) |
Pressure on both low and high pressure sides is high.
Large amount of frost or dew on the low pressure side tubing. |
Faulty expansion valve.
Refrigerant flow is not regulated properly. |
Replace expansion valve. |